MH-411D Industrial NDIR CO2 Sensor

The MH-411D is a compact cylindrical NDIR CO2 sensor for industrial process control, safety equipment, HVAC and agricultural applications. It supports optional ranges up to 10% vol, UART and 0.4–2 V output and fast response below 30 seconds.

BrandWinsen
Sensing PrincipleNDIR
Target GasCO2
Product TypeIndustrial NDIR CO2 Sensor
CO2 Sensing for OEM Integration

Product Overview

Industrial carbon-dioxide measurement in a compact IP54 cylindrical package.

The sensor uses non-dispersive infrared technology to provide selective, oxygen-independent CO2 measurement with internal temperature compensation.

Its safety-barrier power requirement and intrinsic-safety terminal parameters support appropriate protected industrial instrument designs.

Designed for Reliable Integration

Key Features

Optional Range to 10% Vol

Designed for both ppm-level and percentage-level carbon-dioxide measurement.

Fast Response

T90 response time is specified below 30 seconds.

UART and Analog Output

Provides UART communication and a 0.4–2 V analog signal.

Compact Cylindrical Housing

The package measures Ø20 × 22.2 mm.

IP54 Protection

The official specification lists an IP54 defense grade.

Temperature-compensated NDIR

Built-in temperature sensing supports stable linear CO2 output.

Typical Use Cases

Applications

Industrial Process Control
Safety Protection Equipment
HVAC and Refrigeration
Agricultural Monitoring
Animal Husbandry
Official Product Parameters

Technical Specifications

Parameter Specification
Model MH-411D
Detected Gas Carbon dioxide (CO2)
Detection Principle Non-dispersive infrared (NDIR)
Detection Range 0–10% vol optional
Standard Range Options 0–2000 ppm; 0–6000 ppm; 0–1% vol; 0–3% vol; 0–5% vol
Accuracy ±(50 ppm + 5% of reading)
Working Voltage 3.6–5 V DC; safety-barrier power required
Average Current <85 mA
Interface Level 3.0 V
Output Signal UART; 0.4–2 V analog, safety-barrier power required
Warm-up Time 3 min
Response Time T90 <30 s
Operating Temperature -20°C to +60°C
Operating Humidity 0–95% RH, non-condensing
Dimensions Ø20 × 22.2 mm
Weight 35 g
Expected Lifespan >5 years
Protection Grade IP54
Intrinsic-safety Terminal Parameters Ui=7.5 V DC; Ii=265 mA; Pi=0.5 W; Ci=10 μF; Li=0 mH

Specifications are based on the official Winsen product page. Confirm the latest datasheet, communication protocol, calibration requirements and mechanical drawing before final product design.

Need More Information About the MH-411D?

Contact us for the latest datasheet, model selection support, samples and OEM integration information.